SensorAlarm pools the database filled by readsensor and checks for alarm conditions. Alarms are given based on criteria. The table with all criteria and actions is given below.

Alarmconditions

This is the Alarm conditions table that is used in the software.

Sensor Type/Unit Alarm Condition(s) Nr. of samples Mail/SMS who (Software) Action
CCwarm Temp/C > 25 5 obs send mail/SMS
> 28 5 obs send mail/SMS
< 15 5 obs send mail/SMS
CCcold Temp/C
PUMAwarm Temp/C > 28 5 obs send mail/SMS
> 31 5 obs send mail/SMS
< 15 5 obs send mail/SMS
PUMAcold Temp/C
DZBwarm Temp/C > 27 5 obs send mail/SMS
> 30 5 obs send mail/SMS
< 15 5 obs send mail/SMS
DZBcold Temp/C
CONSwarm Temp/C > 27 5 obs send mail/SMS
> 30 5 obs send mail/SMS
< 15 5 obs send mail/SMS
CONScold Temp/C
WATERcold Temp/C
WATERwarm Temp/C > 15 5 obs send mail/SMS
> 18 5 obs send mail/SMS
< 10 5 obs send mail/SMS
CVwarm Temp/C
Sup-He-RTx + Ret-He-RTx Pres/bar < 15 5 obs, stiepel send mail/SMS
PumpMain rpm/% ??? ??? obs send mail/SMS
PumpCC rpm/% ??? ??? obs send mail/SMS
PumpDZB rpm/% ??? ??? obs send mail/SMS
PumpPuma rpm/% ??? ??? obs send mail/SMS
PumpConsole rpm/% ??? ??? obs send mail/SMS
Compressor Power/Kw ??? ???
Brand1 Status 0 1 obs send mail/SMS
Brand2 Status 0 1 obs send mail/SMS
Inbraak Status 0 1 obs send mail/SMS
Net Status 0 1 obs send mail/SMS
CompressorSwitch Status 0 1 obs send mail/SMS
MainPump Status 0 1 obs send mail/SMS
SectorPumps Status 0 1 obs send mail/SMS
Cv Status 0 1 obs send mail/SMS

QR Code